Ventilation Rate Calculator (ASHRAE 62.2)

Calculate the required whole-building mechanical ventilation rate for residential buildings per ASHRAE Standard 62.2-2022.

Formula

ASHRAE 62.2-2022, Equation 4.1a — Whole-Building Ventilation Rate:

Qfan = 0.03 × Afloor + 7.5 × (Nbr + 1)

  • Qfan — Required mechanical ventilation rate (CFM)
  • Afloor — Conditioned floor area (ft²)
  • Nbr — Number of bedrooms (occupants default = Nbr + 1)

Infiltration Credit (Section 4.1.3):

Qnet = max(Qfan − 0.5 × Qinf, 0)

Fan Power: P (W) = Qnet × η (W/CFM)

Annual Energy: E (kWh/yr) = P × 8,760 / 1,000

Assumptions & References

  • Based on ASHRAE Standard 62.2-2022: Ventilation and Acceptable Indoor Air Quality in Residential Buildings.
  • Infiltration credit of up to 50% of measured infiltration (Qinf) may be applied when a blower door test is performed per Section 4.1.3.
  • This calculator covers whole-building ventilation only; local exhaust (kitchen, bath) requirements are addressed separately in Section 5.

In the network