Humidity & Dew Point Calculator

Calculate dew point temperature, absolute humidity, wet-bulb temperature, and vapor pressure from air temperature and relative humidity using the Magnus formula and psychrometric equations.

Formulas Used

1. Saturation Vapor Pressure — Buck Equation:

es(T) = 6.1078 × exp( (17.625 × T) / (243.04 + T) )   [hPa]

2. Dew Point — Magnus Formula Inversion:

γ = ln(RH/100) + (17.625 × T) / (243.04 + T)
Td = 243.04 × γ / (17.625 − γ)   [°C]

3. Absolute Humidity:

AH = 216.7 × ea / TK   [g/m³]
where ea = (RH/100) × es,   TK = T + 273.15

4. Specific Humidity:

q = 621.97 × ea / (P − 0.378 × ea)   [g/kg]

5. Wet-Bulb Temperature — Stull (2011) Empirical:

Tw = T·atan(0.151977·√(RH+8.313659)) + atan(T+RH)
       − atan(RH−1.676331) + 0.00391838·RH1.5·atan(0.023101·RH) − 4.686035

6. Vapor Pressure Deficit:

VPD = es − ea   [hPa]

7. Humidex (Environment Canada):

Humidex = T + 0.5555 × (es(Td) − 10.0)

Assumptions & References

  • Dew point formula accuracy: ±0.35 °C for RH > 50% (Lawrence, 2005, BAMS).
  • Wet-bulb formula: Stull, R. (2011). "Wet-Bulb Temperature from Relative Humidity and Air Temperature." Journal of Applied Meteorology and Climatology, 50(11), 2267–2269. Accuracy ±1 °C for 5–99% RH, −20 to 50 °C.